Abstract
This paper presents a fast calculation method for the tie-line ATC (Available Transfer Capability) with transient stability constraints. In this paper, first, the characteristics of the ATC are drawn in order to reduce the calculation time drastically. Secondly, a novel index for finding critical cases quickly using a transient energy function and a screening method for ranking unstable cases using the stepping-out times are proposed. The method is tested on two IEEJ model systems (EAST 10 machine 47 bus system and EAST 30 machine 107 bus system). The results show the validity of the method.
Original language | English |
---|---|
Title of host publication | 2010 9th International Power and Energy Conference, IPEC 2010 |
Pages | 801-806 |
Number of pages | 6 |
DOIs | |
Publication status | Published - 2010 |
Event | 2010 9th International Power and Energy Conference, IPEC 2010 - Singapore Duration: 2010 Oct 27 → 2010 Oct 29 |
Other
Other | 2010 9th International Power and Energy Conference, IPEC 2010 |
---|---|
City | Singapore |
Period | 10/10/27 → 10/10/29 |
Keywords
- ATC
- Component
- Contingency screening
- Power system transient stability
- Transient energy function
ASJC Scopus subject areas
- Energy Engineering and Power Technology