Analysis of even harmonics generation in an isolated electric power system

Norikazu Kanao, Yasuhiro Hayashi, Junya Matsuki

Research output: Contribution to journalArticle

2 Citations (Scopus)

Abstract

Harmonics bred from loads are mainly odd order because the current waveform has half-wave symmetry. Since the even harmonics are negligibly small, those are not generally measured in electric power systems. However, even harmonics were measured at a 500/275/154 kV substation in Hokuriku Electric Power Company after removal of a transmission line fault. The even harmonics caused malfunctions of protective digital relays because the relays used 4 th harmonics at the input filter as automatic supervisory signal. This paper describes the mechanism of generation of the even harmonics by comparing measured waveforms with ATP-EMTP simulation results. As a result of analysis, it is cleared that even harmonics are generated by three causes. The first cause is a magnetizing current of transformers due to flux deviation by DC component of a fault current. The second one is due to harmonic conversion of a synchronous machine which generates even harmonics when direct current component or even harmonic current flow into the machine. The third one is that increase of harmonic impedance due to an isolated power system produces harmonic voltages. The design of the input filter of protective digital relays should consider even harmonics generation in an isolated power system.

Original languageEnglish
Pages (from-to)887-893
Number of pages7
JournalIEEJ Transactions on Power and Energy
Volume126
Issue number9
DOIs
Publication statusPublished - 2006
Externally publishedYes

Fingerprint

Electric fault currents
Adenosinetriphosphate
Harmonic generation
Electric power systems
Electric lines
Fluxes
Electric potential
Industry

Keywords

  • DC current
  • EMTP
  • Even harmonics
  • Harmonic impedance
  • Magnetizing current
  • Synchronous machine

ASJC Scopus subject areas

  • Electrical and Electronic Engineering
  • Energy Engineering and Power Technology

Cite this

Analysis of even harmonics generation in an isolated electric power system. / Kanao, Norikazu; Hayashi, Yasuhiro; Matsuki, Junya.

In: IEEJ Transactions on Power and Energy, Vol. 126, No. 9, 2006, p. 887-893.

Research output: Contribution to journalArticle

@article{715be9d2e13440568375c3fde7daa79c,
title = "Analysis of even harmonics generation in an isolated electric power system",
abstract = "Harmonics bred from loads are mainly odd order because the current waveform has half-wave symmetry. Since the even harmonics are negligibly small, those are not generally measured in electric power systems. However, even harmonics were measured at a 500/275/154 kV substation in Hokuriku Electric Power Company after removal of a transmission line fault. The even harmonics caused malfunctions of protective digital relays because the relays used 4 th harmonics at the input filter as automatic supervisory signal. This paper describes the mechanism of generation of the even harmonics by comparing measured waveforms with ATP-EMTP simulation results. As a result of analysis, it is cleared that even harmonics are generated by three causes. The first cause is a magnetizing current of transformers due to flux deviation by DC component of a fault current. The second one is due to harmonic conversion of a synchronous machine which generates even harmonics when direct current component or even harmonic current flow into the machine. The third one is that increase of harmonic impedance due to an isolated power system produces harmonic voltages. The design of the input filter of protective digital relays should consider even harmonics generation in an isolated power system.",
keywords = "DC current, EMTP, Even harmonics, Harmonic impedance, Magnetizing current, Synchronous machine",
author = "Norikazu Kanao and Yasuhiro Hayashi and Junya Matsuki",
year = "2006",
doi = "10.1541/ieejpes.126.887",
language = "English",
volume = "126",
pages = "887--893",
journal = "IEEJ Transactions on Power and Energy",
issn = "0385-4213",
publisher = "The Institute of Electrical Engineers of Japan",
number = "9",

}

TY - JOUR

T1 - Analysis of even harmonics generation in an isolated electric power system

AU - Kanao, Norikazu

AU - Hayashi, Yasuhiro

AU - Matsuki, Junya

PY - 2006

Y1 - 2006

N2 - Harmonics bred from loads are mainly odd order because the current waveform has half-wave symmetry. Since the even harmonics are negligibly small, those are not generally measured in electric power systems. However, even harmonics were measured at a 500/275/154 kV substation in Hokuriku Electric Power Company after removal of a transmission line fault. The even harmonics caused malfunctions of protective digital relays because the relays used 4 th harmonics at the input filter as automatic supervisory signal. This paper describes the mechanism of generation of the even harmonics by comparing measured waveforms with ATP-EMTP simulation results. As a result of analysis, it is cleared that even harmonics are generated by three causes. The first cause is a magnetizing current of transformers due to flux deviation by DC component of a fault current. The second one is due to harmonic conversion of a synchronous machine which generates even harmonics when direct current component or even harmonic current flow into the machine. The third one is that increase of harmonic impedance due to an isolated power system produces harmonic voltages. The design of the input filter of protective digital relays should consider even harmonics generation in an isolated power system.

AB - Harmonics bred from loads are mainly odd order because the current waveform has half-wave symmetry. Since the even harmonics are negligibly small, those are not generally measured in electric power systems. However, even harmonics were measured at a 500/275/154 kV substation in Hokuriku Electric Power Company after removal of a transmission line fault. The even harmonics caused malfunctions of protective digital relays because the relays used 4 th harmonics at the input filter as automatic supervisory signal. This paper describes the mechanism of generation of the even harmonics by comparing measured waveforms with ATP-EMTP simulation results. As a result of analysis, it is cleared that even harmonics are generated by three causes. The first cause is a magnetizing current of transformers due to flux deviation by DC component of a fault current. The second one is due to harmonic conversion of a synchronous machine which generates even harmonics when direct current component or even harmonic current flow into the machine. The third one is that increase of harmonic impedance due to an isolated power system produces harmonic voltages. The design of the input filter of protective digital relays should consider even harmonics generation in an isolated power system.

KW - DC current

KW - EMTP

KW - Even harmonics

KW - Harmonic impedance

KW - Magnetizing current

KW - Synchronous machine

UR - http://www.scopus.com/inward/record.url?scp=33748555842&partnerID=8YFLogxK

UR - http://www.scopus.com/inward/citedby.url?scp=33748555842&partnerID=8YFLogxK

U2 - 10.1541/ieejpes.126.887

DO - 10.1541/ieejpes.126.887

M3 - Article

AN - SCOPUS:33748555842

VL - 126

SP - 887

EP - 893

JO - IEEJ Transactions on Power and Energy

JF - IEEJ Transactions on Power and Energy

SN - 0385-4213

IS - 9

ER -