Effects of reducing internal heat load on the operation of multi-split type air conditioning system in an office

Sayana Tsushima, Shuhei Takahashi, Emi Takai, Junta Fujisawa, Shinichi Tanabe, Hiromasa Tanaka, Hisataka Kitora

    Research output: Chapter in Book/Report/Conference proceedingConference contribution

    Abstract

    In this study, the internal heat load and operation of an HVAC system were investigated in an office drawing low internal heat load where multi-split type air conditioning system were adopted. Field and questionnaire surveys and an energy consumption analysis were performed. The designed total cooling capacity of the HVAC system was 158 W/m2, relatively small compared to most systems that have had a 200 W/m2 capacity. However, the average load factor was below 30%. Moreover, it was found that the operation of a dedicated outdoor air system had a large influence on the total electric energy consumption in offices practicing internal load reduction, and that the main cause for the operation change was the humidity setting of the system. Introducing air-conditioning systems with an appropriate smaller capacity and a comprehensive energy-saving operation method, rather than partially optimizing each device, would be beneficial in terms of total energy saving.

    Original languageEnglish
    Title of host publicationHealthy Buildings Europe 2017
    PublisherInternational Society of Indoor Air Quality and Climate
    ISBN (Print)9788379472604
    Publication statusPublished - 2017 Jan 1
    EventHealthy Buildings Europe 2017, HB 2017 - Lublin, Poland
    Duration: 2017 Jul 22017 Jul 5

    Other

    OtherHealthy Buildings Europe 2017, HB 2017
    CountryPoland
    CityLublin
    Period17/7/217/7/5

    Fingerprint

    Thermal load
    Air conditioning
    Energy conservation
    Energy utilization
    Atmospheric humidity
    Cooling
    Air
    HVAC

    Keywords

    • Air conditioning (HVAC) system
    • Energy consumption
    • Heating
    • Low internal heat load office
    • Ventilation

    ASJC Scopus subject areas

    • Civil and Structural Engineering

    Cite this

    Tsushima, S., Takahashi, S., Takai, E., Fujisawa, J., Tanabe, S., Tanaka, H., & Kitora, H. (2017). Effects of reducing internal heat load on the operation of multi-split type air conditioning system in an office. In Healthy Buildings Europe 2017 International Society of Indoor Air Quality and Climate.

    Effects of reducing internal heat load on the operation of multi-split type air conditioning system in an office. / Tsushima, Sayana; Takahashi, Shuhei; Takai, Emi; Fujisawa, Junta; Tanabe, Shinichi; Tanaka, Hiromasa; Kitora, Hisataka.

    Healthy Buildings Europe 2017. International Society of Indoor Air Quality and Climate, 2017.

    Research output: Chapter in Book/Report/Conference proceedingConference contribution

    Tsushima, S, Takahashi, S, Takai, E, Fujisawa, J, Tanabe, S, Tanaka, H & Kitora, H 2017, Effects of reducing internal heat load on the operation of multi-split type air conditioning system in an office. in Healthy Buildings Europe 2017. International Society of Indoor Air Quality and Climate, Healthy Buildings Europe 2017, HB 2017, Lublin, Poland, 17/7/2.
    Tsushima S, Takahashi S, Takai E, Fujisawa J, Tanabe S, Tanaka H et al. Effects of reducing internal heat load on the operation of multi-split type air conditioning system in an office. In Healthy Buildings Europe 2017. International Society of Indoor Air Quality and Climate. 2017
    Tsushima, Sayana ; Takahashi, Shuhei ; Takai, Emi ; Fujisawa, Junta ; Tanabe, Shinichi ; Tanaka, Hiromasa ; Kitora, Hisataka. / Effects of reducing internal heat load on the operation of multi-split type air conditioning system in an office. Healthy Buildings Europe 2017. International Society of Indoor Air Quality and Climate, 2017.
    @inproceedings{46fc381ac64c43869bfd7c0c2ef3193e,
    title = "Effects of reducing internal heat load on the operation of multi-split type air conditioning system in an office",
    abstract = "In this study, the internal heat load and operation of an HVAC system were investigated in an office drawing low internal heat load where multi-split type air conditioning system were adopted. Field and questionnaire surveys and an energy consumption analysis were performed. The designed total cooling capacity of the HVAC system was 158 W/m2, relatively small compared to most systems that have had a 200 W/m2 capacity. However, the average load factor was below 30{\%}. Moreover, it was found that the operation of a dedicated outdoor air system had a large influence on the total electric energy consumption in offices practicing internal load reduction, and that the main cause for the operation change was the humidity setting of the system. Introducing air-conditioning systems with an appropriate smaller capacity and a comprehensive energy-saving operation method, rather than partially optimizing each device, would be beneficial in terms of total energy saving.",
    keywords = "Air conditioning (HVAC) system, Energy consumption, Heating, Low internal heat load office, Ventilation",
    author = "Sayana Tsushima and Shuhei Takahashi and Emi Takai and Junta Fujisawa and Shinichi Tanabe and Hiromasa Tanaka and Hisataka Kitora",
    year = "2017",
    month = "1",
    day = "1",
    language = "English",
    isbn = "9788379472604",
    booktitle = "Healthy Buildings Europe 2017",
    publisher = "International Society of Indoor Air Quality and Climate",

    }

    TY - GEN

    T1 - Effects of reducing internal heat load on the operation of multi-split type air conditioning system in an office

    AU - Tsushima, Sayana

    AU - Takahashi, Shuhei

    AU - Takai, Emi

    AU - Fujisawa, Junta

    AU - Tanabe, Shinichi

    AU - Tanaka, Hiromasa

    AU - Kitora, Hisataka

    PY - 2017/1/1

    Y1 - 2017/1/1

    N2 - In this study, the internal heat load and operation of an HVAC system were investigated in an office drawing low internal heat load where multi-split type air conditioning system were adopted. Field and questionnaire surveys and an energy consumption analysis were performed. The designed total cooling capacity of the HVAC system was 158 W/m2, relatively small compared to most systems that have had a 200 W/m2 capacity. However, the average load factor was below 30%. Moreover, it was found that the operation of a dedicated outdoor air system had a large influence on the total electric energy consumption in offices practicing internal load reduction, and that the main cause for the operation change was the humidity setting of the system. Introducing air-conditioning systems with an appropriate smaller capacity and a comprehensive energy-saving operation method, rather than partially optimizing each device, would be beneficial in terms of total energy saving.

    AB - In this study, the internal heat load and operation of an HVAC system were investigated in an office drawing low internal heat load where multi-split type air conditioning system were adopted. Field and questionnaire surveys and an energy consumption analysis were performed. The designed total cooling capacity of the HVAC system was 158 W/m2, relatively small compared to most systems that have had a 200 W/m2 capacity. However, the average load factor was below 30%. Moreover, it was found that the operation of a dedicated outdoor air system had a large influence on the total electric energy consumption in offices practicing internal load reduction, and that the main cause for the operation change was the humidity setting of the system. Introducing air-conditioning systems with an appropriate smaller capacity and a comprehensive energy-saving operation method, rather than partially optimizing each device, would be beneficial in terms of total energy saving.

    KW - Air conditioning (HVAC) system

    KW - Energy consumption

    KW - Heating

    KW - Low internal heat load office

    KW - Ventilation

    UR - http://www.scopus.com/inward/record.url?scp=85053919910&partnerID=8YFLogxK

    UR - http://www.scopus.com/inward/citedby.url?scp=85053919910&partnerID=8YFLogxK

    M3 - Conference contribution

    SN - 9788379472604

    BT - Healthy Buildings Europe 2017

    PB - International Society of Indoor Air Quality and Climate

    ER -