Abstract
The correlation between charge distribution in aged XLPE cable and location of water tree have been studied. The space charge radial distribution and different angular location in the insulating wall of service aged XLPE cable, induced by application of a dc stress, was measured using the pulsed electro-acoustic (PEA) method. Furthermore, a cross-section of sliced insulating wall was observed with optical microscope to compare with the radial space charge distribution. The cable under investigation was electrically aged in service at the 6.6kV for 25 years in wet conditions. Results of both observation of the space charge distribution and location of water tree, the water tree was found at the angular location in which the space charge was observed. On the other hand, the water tree was not found at the angular location in which the space charge was never observed. Judging from the results, the space charge measurement of PEA method seems to be useful for the diagnosis of the water tree in aged cable.
Original language | English |
---|---|
Title of host publication | Conference on Electrical Insulation and Dielectric Phenomena (CEIDP), Annual Report |
Publisher | IEEE |
Pages | 630-633 |
Number of pages | 4 |
Volume | 2 |
Publication status | Published - 1999 |
Externally published | Yes |
Event | Proceedings of the 1999 68th Annual Conference on Electrical Insulation and Dielectric Phenomena (1999 CEIDP) - Austin, TX, USA Duration: 1999 Oct 17 → 1999 Oct 20 |
Other
Other | Proceedings of the 1999 68th Annual Conference on Electrical Insulation and Dielectric Phenomena (1999 CEIDP) |
---|---|
City | Austin, TX, USA |
Period | 99/10/17 → 99/10/20 |
Fingerprint
ASJC Scopus subject areas
- Electrical and Electronic Engineering
- Industrial and Manufacturing Engineering
- Building and Construction
Cite this
Space charge distribution measurement in XLPE cable for detection of the water tree location. / Suzuki, Kentarou; Tanaka, Yasuhiro; Takada, Tatsuo; Ohki, Yoshimichi; Takeya, Chikashi.
Conference on Electrical Insulation and Dielectric Phenomena (CEIDP), Annual Report. Vol. 2 IEEE, 1999. p. 630-633.Research output: Chapter in Book/Report/Conference proceeding › Conference contribution
}
TY - GEN
T1 - Space charge distribution measurement in XLPE cable for detection of the water tree location
AU - Suzuki, Kentarou
AU - Tanaka, Yasuhiro
AU - Takada, Tatsuo
AU - Ohki, Yoshimichi
AU - Takeya, Chikashi
PY - 1999
Y1 - 1999
N2 - The correlation between charge distribution in aged XLPE cable and location of water tree have been studied. The space charge radial distribution and different angular location in the insulating wall of service aged XLPE cable, induced by application of a dc stress, was measured using the pulsed electro-acoustic (PEA) method. Furthermore, a cross-section of sliced insulating wall was observed with optical microscope to compare with the radial space charge distribution. The cable under investigation was electrically aged in service at the 6.6kV for 25 years in wet conditions. Results of both observation of the space charge distribution and location of water tree, the water tree was found at the angular location in which the space charge was observed. On the other hand, the water tree was not found at the angular location in which the space charge was never observed. Judging from the results, the space charge measurement of PEA method seems to be useful for the diagnosis of the water tree in aged cable.
AB - The correlation between charge distribution in aged XLPE cable and location of water tree have been studied. The space charge radial distribution and different angular location in the insulating wall of service aged XLPE cable, induced by application of a dc stress, was measured using the pulsed electro-acoustic (PEA) method. Furthermore, a cross-section of sliced insulating wall was observed with optical microscope to compare with the radial space charge distribution. The cable under investigation was electrically aged in service at the 6.6kV for 25 years in wet conditions. Results of both observation of the space charge distribution and location of water tree, the water tree was found at the angular location in which the space charge was observed. On the other hand, the water tree was not found at the angular location in which the space charge was never observed. Judging from the results, the space charge measurement of PEA method seems to be useful for the diagnosis of the water tree in aged cable.
UR - http://www.scopus.com/inward/record.url?scp=0033308684&partnerID=8YFLogxK
UR - http://www.scopus.com/inward/citedby.url?scp=0033308684&partnerID=8YFLogxK
M3 - Conference contribution
AN - SCOPUS:0033308684
VL - 2
SP - 630
EP - 633
BT - Conference on Electrical Insulation and Dielectric Phenomena (CEIDP), Annual Report
PB - IEEE
ER -