原子力発電所から撤去された FR-EPDM ケーブルの重大事故環境下における絶縁性能

Aiki Watanabe*, Asuka Haga, Takefumi Minakawa, Masaaki Ikeda, Naoshi Hirai, Yoshimichi Ohki

*この研究の対応する著者

研究成果: Article査読

抄録

The insulation performance of cables removed from an actual plant was investigated in a simulated severe accident (SA) environment. The cable insulated with flame-retardant ethylene propylene diene rubber (FR-EPDM) was a safety cable in the plant. A similar FR-EPDM-insulated cable was aged artificially to the degree equivalent to what the removed cable would have been suffered. These cables were irradiated with 60Co gamma rays at a dose rate of 10 kGy/h for 50 hours at room temperature to simulate the radiation exposure during a SA. The cables were then exposed to a steam environment for 168 hours to simulate the SA. During the steam exposure, the insulation resistance of the cables was measured continuously. As a result, the minimum insulation resistance was about 108 to 109 Ωm in the two cables, indicating that both have sufficient insulation performance.

寄稿の翻訳タイトルInsulation Performance of a Cable Insulated with Flame-retardant Ethylene-propylene-diene Rubber Removed from a Nuclear Power Plant under Severe Accident Conditions
本文言語Japanese
ページ(範囲)368-374
ページ数7
ジャーナルIEEJ Transactions on Fundamentals and Materials
142
9
DOI
出版ステータスPublished - 2022

Keywords

  • cable
  • insulation performance
  • nuclear power plant
  • severe accident