TY - JOUR
T1 - Analysis of power quality based on real data and quality improvement at campus distribution system
AU - Kawasaki, Shoji
AU - Matsuki, Junya
AU - Hayashi, Yasuhiro
AU - Ito, Akitoshi
PY - 2009
Y1 - 2009
N2 - In recent years, a lot of equipments have been made using the inverter technology from home electric appliances to office automation apparatuses and industrial equipments with the development of power electronics technology. The voltage distortion of a distribution system has increased due to the harmonic currents generated from these apparatuses, and the increase in harmonics continues to be expected. In addition, the distribution system forms the circuit of harmonic distortion expansion by the prevalence of static capacitor without L for power factor improvement. Moreover, the voltage imbalance occurs by diversification of loads or imbalanced connection of single-phase loads. The deterioration of power quality in the distribution system causes various problems such as the overheating of equipments and malfunction of rotating machines. Since the power quality changes according to air temperature and date, it is desirable to measure the voltages and currents continuously for a long time. In this study, the authors focus attention on the distribution system in the University of Fukui campus, and the authors have measured the voltages and currents in the distribution system for a long period with WAMS (Wide Area Measurement System) using NCT (Network Computing Terminal). Based on the obtained data, the authors analyzed the power quality of the campus distribution system from viewpoints of voltage imbalance, current imbalance, voltage THD (Total Harmonic Distortion), and current THD. Furthermore, the improvement effect of power quality of the campus distribution system by exchange of single-phase load connection is described.
AB - In recent years, a lot of equipments have been made using the inverter technology from home electric appliances to office automation apparatuses and industrial equipments with the development of power electronics technology. The voltage distortion of a distribution system has increased due to the harmonic currents generated from these apparatuses, and the increase in harmonics continues to be expected. In addition, the distribution system forms the circuit of harmonic distortion expansion by the prevalence of static capacitor without L for power factor improvement. Moreover, the voltage imbalance occurs by diversification of loads or imbalanced connection of single-phase loads. The deterioration of power quality in the distribution system causes various problems such as the overheating of equipments and malfunction of rotating machines. Since the power quality changes according to air temperature and date, it is desirable to measure the voltages and currents continuously for a long time. In this study, the authors focus attention on the distribution system in the University of Fukui campus, and the authors have measured the voltages and currents in the distribution system for a long period with WAMS (Wide Area Measurement System) using NCT (Network Computing Terminal). Based on the obtained data, the authors analyzed the power quality of the campus distribution system from viewpoints of voltage imbalance, current imbalance, voltage THD (Total Harmonic Distortion), and current THD. Furthermore, the improvement effect of power quality of the campus distribution system by exchange of single-phase load connection is described.
KW - Campus distribution system
KW - Current imbalance rate
KW - Current total harmonic distortion
KW - Power quality
KW - Voltage imbalance rate
KW - Voltage total harmonic distortion
KW - Wide area measurement system
UR - http://www.scopus.com/inward/record.url?scp=70350555602&partnerID=8YFLogxK
UR - http://www.scopus.com/inward/citedby.url?scp=70350555602&partnerID=8YFLogxK
U2 - 10.1541/ieejpes.129.1115
DO - 10.1541/ieejpes.129.1115
M3 - Article
AN - SCOPUS:70350555602
VL - 129
SP - 1115-1122+6
JO - IEEJ Transactions on Power and Energy
JF - IEEJ Transactions on Power and Energy
SN - 0385-4213
IS - 9