Cooperative voltage control method by power factor control of PV systems and LRT

Shoji Kawasaki*, Noriaki Kanemoto, Hisao Taoka, Junya Matsuki, Yasuhiro Hayashi

*この研究の対応する著者

研究成果: Article査読

32 被引用数 (Scopus)

抄録

Recently, the number of system interconnection of the renewable energy sources (RES) such as the photovoltaic generation (PV) and wind power generation is increasing drastically, and there is in danger of changing the voltages in a distribution system by the precipitous output variation of RESs. In this study, the authors propose one voltage control method of the distribution system by the power factor control of plural PV systems in consideration of cooperation with the load ratio control transformer (LRT) of laggard control response installed beforehand in the distribution system. In the proposed method, the slow voltage variation is controlled by LRT, and the steep voltage variation uncontrollable by LRT is controlled by plural PV systems, as a result, all the node voltages are controllable within the proper limits. In order to verify the validity of the proposed method, the numerical calculations are carried out by using an analytical model of distribution system which interconnected PV systems.

本文言語English
ページ(範囲)309-316
ページ数8
ジャーナルIEEJ Transactions on Power and Energy
132
4
DOI
出版ステータスPublished - 2012

ASJC Scopus subject areas

  • エネルギー工学および電力技術
  • 電子工学および電気工学

フィンガープリント

「Cooperative voltage control method by power factor control of PV systems and LRT」の研究トピックを掘り下げます。これらがまとまってユニークなフィンガープリントを構成します。

引用スタイル