Design and evaluation of 66 kV-class "3-in-One" HTS cable using REBCO wires

M. Ohya, H. Hirota, T. Masuda, N. Amemiya, A. Ishiyama, T. Ohkuma

研究成果: Conference article

5 引用 (Scopus)

抜粋

Sumitomo Electric (SEI) has been involved in the development of 66 kV-class HTS cables using REBCO wires. One of the technical targets is to reduce the AC loss to less than 2 W/m/phase at 5 kA. SEI has developed a clad-type textured metal substrate with lower magnetization loss than NiW substrate. REBCO tapes 30 mm-wide were slit into 4 mm-wide strips, and these strips were wound spirally on a former with small gaps. The measured AC loss of the manufactured cable was 1.8 W/m/phase at 5 kA, achieving the AC loss goal.

元の言語English
ページ(範囲)849-854
ページ数6
ジャーナルPhysics Procedia
36
DOI
出版物ステータスPublished - 2012 1 1
イベントSuperconductivity Centennial Conference, SCC 2011 - The Hague, Netherlands
継続期間: 2011 9 182011 9 23

ASJC Scopus subject areas

  • Physics and Astronomy(all)

フィンガープリント Design and evaluation of 66 kV-class "3-in-One" HTS cable using REBCO wires' の研究トピックを掘り下げます。これらはともに一意のフィンガープリントを構成します。

  • これを引用