This paper presents a distribution automation system (DAS) for service restoration in the distribution network with photovoltaic (PV) generator systems, which are disconnected simultaneously after a fault and subsequently reconnected after service restoration. Because the reverse power flow of PVs affects voltage in the distribution system, voltage dips and surges occur during the service restoration. However, current DAS do not control voltage regulators such as an on-load tap changer (OLTC) and step voltage regulators (SVRs) during the service restoration. The proposed DAS estimates the voltage in a distribution network considering the simultaneous disconnection of PVs by performing power flow calculations, and it controls the tap position of OLTC and/or SVRs according to the predicted voltage deviation. The voltage after the disconnection of PVs is calculated by estimating the PV output utilizing square kilometer solar radiation data calculated using satellite image data in real time.