Failure aspects of electronic watt-hour meters due to direct lightning strikes to distribution lines - Electromagnetic disturbance caused by lightning current flowing through watt-hour meters and its countermeasure-

Kazuyuki Ishimoto, Ryota Mori, Akira Asakawa, Yoshimichi Ohki

    研究成果: Article

    抜粋

    Recently, advanced "smart meters" have been introduced widely to electric power distribution lines. Since smart meters consist of many low-voltage electronic devices, their vulnerability to disturbances such as lightning surges is a matter of concern. Therefore, to establish an effective lightning protection countermeasure against these disturbances, we have been investigating the lightning failure aspects of electronic watt-hour meters (WHMs), which have a function similar to that of a watt-meter section in smart meters. In this paper, we explored countermeasures for improving the performance of WHMs against the lightning transient magnetic fields. At first, we examined the performance of WHMs by lightning impulse current tests. As a result, it has become clear that the increase in distance between a bus conductor and a processing unit and magnetic shield of a processing unit are effective in reducing the probability of failures caused by the transient magnetic fields. Next, we proposed a calculation method of the lightning failure rate of WHMs based on a lightning surge analysis. The calculation results indicate that the failure occurs more frequently by subsequent strokes than by first strokes or if the grounding resistance of a pole transformer is higher.

    元の言語English
    ページ(範囲)766-776
    ページ数11
    ジャーナルIEEJ Transactions on Power and Energy
    137
    発行部数12
    DOI
    出版物ステータスPublished - 2017 1 1

      フィンガープリント

    ASJC Scopus subject areas

    • Energy Engineering and Power Technology
    • Electrical and Electronic Engineering

    これを引用