Fundamental evaluation of the performance field experiment and model experiment of air-conditioning system with floor thermal storage

Jeongsoo Kim, Hajime Matsuura, Shinichi Tanabe

    研究成果: Article

    2 引用 (Scopus)

    抄録

    Fundamental evaluation of the performance field experiment and model experiment of air-conditioning system with floor thermal storage were analysed on following 3 aspects. 1) The temperature distribution to the floor slab was able to be confirmed by the distributed temperature sensor on the field measured data. 2) The domination of the system was able to be verified by understanding the building heat characteristic based on the comparison of a variety driving patterns. 3) The influence that the supply temperature and the supply distance gave to the amount of the thermal storage was able to be confirmed by the model experiment.

    元の言語English
    ページ(範囲)63-70
    ページ数8
    ジャーナルJournal of Environmental Engineering
    74
    発行部数635
    DOI
    出版物ステータスPublished - 2009 1

    Fingerprint

    Air conditioning
    Experiments
    Temperature sensors
    Temperature distribution
    Hot Temperature
    Temperature

    ASJC Scopus subject areas

    • Environmental Engineering

    これを引用

    @article{d0fdf7ecddd148bcb29667ca976dd66e,
    title = "Fundamental evaluation of the performance field experiment and model experiment of air-conditioning system with floor thermal storage",
    abstract = "Fundamental evaluation of the performance field experiment and model experiment of air-conditioning system with floor thermal storage were analysed on following 3 aspects. 1) The temperature distribution to the floor slab was able to be confirmed by the distributed temperature sensor on the field measured data. 2) The domination of the system was able to be verified by understanding the building heat characteristic based on the comparison of a variety driving patterns. 3) The influence that the supply temperature and the supply distance gave to the amount of the thermal storage was able to be confirmed by the model experiment.",
    keywords = "Distributed temperature sensor, Field experiment, Floor thermal storage, Model experiment",
    author = "Jeongsoo Kim and Hajime Matsuura and Shinichi Tanabe",
    year = "2009",
    month = "1",
    doi = "10.3130/aije.74.63",
    language = "English",
    volume = "74",
    pages = "63--70",
    journal = "Journal of Environmental Engineering, ASCE",
    issn = "1348-0685",
    publisher = "American Society of Civil Engineers (ASCE)",
    number = "635",

    }

    TY - JOUR

    T1 - Fundamental evaluation of the performance field experiment and model experiment of air-conditioning system with floor thermal storage

    AU - Kim, Jeongsoo

    AU - Matsuura, Hajime

    AU - Tanabe, Shinichi

    PY - 2009/1

    Y1 - 2009/1

    N2 - Fundamental evaluation of the performance field experiment and model experiment of air-conditioning system with floor thermal storage were analysed on following 3 aspects. 1) The temperature distribution to the floor slab was able to be confirmed by the distributed temperature sensor on the field measured data. 2) The domination of the system was able to be verified by understanding the building heat characteristic based on the comparison of a variety driving patterns. 3) The influence that the supply temperature and the supply distance gave to the amount of the thermal storage was able to be confirmed by the model experiment.

    AB - Fundamental evaluation of the performance field experiment and model experiment of air-conditioning system with floor thermal storage were analysed on following 3 aspects. 1) The temperature distribution to the floor slab was able to be confirmed by the distributed temperature sensor on the field measured data. 2) The domination of the system was able to be verified by understanding the building heat characteristic based on the comparison of a variety driving patterns. 3) The influence that the supply temperature and the supply distance gave to the amount of the thermal storage was able to be confirmed by the model experiment.

    KW - Distributed temperature sensor

    KW - Field experiment

    KW - Floor thermal storage

    KW - Model experiment

    UR - http://www.scopus.com/inward/record.url?scp=79954491391&partnerID=8YFLogxK

    UR - http://www.scopus.com/inward/citedby.url?scp=79954491391&partnerID=8YFLogxK

    U2 - 10.3130/aije.74.63

    DO - 10.3130/aije.74.63

    M3 - Article

    AN - SCOPUS:79954491391

    VL - 74

    SP - 63

    EP - 70

    JO - Journal of Environmental Engineering, ASCE

    JF - Journal of Environmental Engineering, ASCE

    SN - 1348-0685

    IS - 635

    ER -