Over-current characteristics of 66-kV RE123 HTS power cable

Xudong Wang*, Atsushi Ishiyama, Masayoshi Ohya, Noboru Fujiwara

*この研究の対応する著者

研究成果査読

16 被引用数 (Scopus)

抄録

In Japan, the development of the 66-kV-class superconducting power cable was begun in 2008 as a national project. A high-temperature superconducting (HTS) power cable typically consists of a copper former, HTS conductor layers, electrical insulation layers, HTS shield layers, and copper shield layers. 66-kV-class superconducting power cables may be subjected to a fault current of 31.5 kArms for 2 s. Therefore, in order to ensure the stability and feasibility of superconducting power cables, we need to investigate these cables with respect to their thermal characteristics and current distribution under fault conditions. In this study, we carried out over-current experiments on a 2-m-long HTS model cable. We also performed numerical simulations on the model cable by using a computer program developed by us on the basis of a 3D finite element method (FEM) and an electrical circuit model.

本文言語English
論文番号5675745
ページ(範囲)1013-1016
ページ数4
ジャーナルIEEE Transactions on Applied Superconductivity
21
3 PART 2
DOI
出版ステータスPublished - 2011 6

ASJC Scopus subject areas

  • 電子材料、光学材料、および磁性材料
  • 凝縮系物理学
  • 電子工学および電気工学

フィンガープリント

「Over-current characteristics of 66-kV RE123 HTS power cable」の研究トピックを掘り下げます。これらがまとまってユニークなフィンガープリントを構成します。