Partial discharge locating system for GIS

H. Maekawa, T. Masui, Hiroshi Inujima, N. Miyamoto

研究成果: Conference contribution

6 引用 (Scopus)

抜粋

Presently detecting of partial discharge (PD) in gas insulated switchgear(GIS) is one of important monitoring terms. This paper describes the study of behavior of surge due to PD in GIS. PD can be detected by catching the electromagnetic wave radiating from the insulated spacer between enclosures, because coaxial between central conductor and enclosure is not completely in insulating spacer part. Antenna can be caught the electromagnetic wave. By catching the several waves from different propagating paths in the same time, PD location in GIS can be estimated. This system we have developed is applied to actual 500kV GIS sw/s.

元の言語English
ホスト出版物のタイトルIEE Conference Publication
編集者 Anon
出版者Publ by IEE
ページ159-163
ページ数5
1
エディション388
出版物ステータスPublished - 1994
外部発表Yes
イベントProceedings of the 2nd International Conference on Advances in Power System Control, Operation & Management - Hong Kong, Hong Kong
継続期間: 1993 12 71993 12 10

Other

OtherProceedings of the 2nd International Conference on Advances in Power System Control, Operation & Management
Hong Kong, Hong Kong
期間93/12/793/12/10