Space charge distribution measurement in XLPE cable for detection of the water tree location

Kentarou Suzuki, Yasuhiro Tanaka, Tatsuo Takada, Yoshimichi Ohki, Chikashi Takeya

研究成果: Conference article

抜粋

The correlation between charge distribution in aged XLPE cable and location of water tree have been studied. The space charge radial distribution and different angular location in the insulating wall of service aged XLPE cable, induced by application of a dc stress, was measured using the pulsed electro-acoustic (PEA) method. Furthermore, a cross-section of sliced insulating wall was observed with optical microscope to compare with the radial space charge distribution. The cable under investigation was electrically aged in service at the 6.6kV for 25 years in wet conditions. Results of both observation of the space charge distribution and location of water tree, the water tree was found at the angular location in which the space charge was observed. On the other hand, the water tree was not found at the angular location in which the space charge was never observed. Judging from the results, the space charge measurement of PEA method seems to be useful for the diagnosis of the water tree in aged cable.

元の言語English
ページ(範囲)630-633
ページ数4
ジャーナルConference on Electrical Insulation and Dielectric Phenomena (CEIDP), Annual Report
2
出版物ステータスPublished - 1999 12 1
イベントProceedings of the 1999 68th Annual Conference on Electrical Insulation and Dielectric Phenomena (1999 CEIDP) - Austin, TX, USA
継続期間: 1999 10 171999 10 20

    フィンガープリント

ASJC Scopus subject areas

  • Electrical and Electronic Engineering
  • Industrial and Manufacturing Engineering
  • Building and Construction

これを引用