Thermal comfort aspects of cold air distribution system

Masaki Shioya, Shinichi Tanabe, Noriyasu Sagara, Yuji Tsubota, Katsuhiro Miura, Ryuji Yanagihara

研究成果: Conference contribution

2 引用 (Scopus)

抜粋

An ice storage system can supply chilled water at approximately 0°C (32°F) to 4°C (39.2°F) to air-handling units. A cold-air distribution system supplies air between 8°C (46.4°F) and 10°C (50°F), which is cooled with the chilled water from an ice storage tank, directly into an air-conditioned space. The system allows large temperature differentials, enabling a considerable reduction in initial and running costs for distribution equipment such as fans and air-handling units. However, there are some concerns about the direct supply of cold air to occupied zones. Draft is one of the major concerns with direct cold air diffusion. The authors conducted draft evaluation experiments with a thermal manikin and also conducted experiments with subjects to prove the manikin results, especially under the best and worst diffusion conditions, based on the manikin experiments. The results showed that air cooled to 7°C (44.6°F) and 8°C (46.4°F) caused no draft that annoyed occupants when used with conventional circular ceiling diffusers.

元の言語English
ホスト出版物のタイトルASHRAE Transactions
出版者ASHRAE
ページ61-72
ページ数12
101
エディションPt 2
出版物ステータスPublished - 1995
外部発表Yes
イベントProceedings of the 1995 ASHRAE Annual Meeting - San Diego, CA, USA
継続期間: 1995 6 241995 6 28

Other

OtherProceedings of the 1995 ASHRAE Annual Meeting
San Diego, CA, USA
期間95/6/2495/6/28

    フィンガープリント

ASJC Scopus subject areas

  • Fluid Flow and Transfer Processes

これを引用

Shioya, M., Tanabe, S., Sagara, N., Tsubota, Y., Miura, K., & Yanagihara, R. (1995). Thermal comfort aspects of cold air distribution system. : ASHRAE Transactions (Pt 2 版, 巻 101, pp. 61-72). ASHRAE.